Buy our

Power line filter for shielded cabinet

power line filters for shielded cabinet icon 1

Series

The 8050 series Power line filters for shielded cabinets is a superior filter housed in a two-compartment casing that achieves 100 dB shielding performance at 14 kHz till 40 GHz. The circuit is designed as a double-circuit with high-quality rod cores providing inductance. 

This series of power line filters are specially designed for a well-grounded shielded cabinet with a rated voltage of 250 VAC / 50-60 Hz. It is compact and in compliance with Class B and C standards for the shielded cabinet. The 8050 series is particularly suitable for use in MRI rooms.

This series is only offered as a two-line filter (phase and neutral).


Product range
  Type IR (A) I Leakage (mA) * Outline drawing Shielding Effectiveness (dB)
8050-2-16 2×16
(DC 70%)
<3 1 100 dB,
14 kHz -
40 GHz
8050-2-32 2x32
(DC 70%)
<5 2
8051-2-16 2x16
(DC 70%)
<3 1

*If the voltage between neutral and earth is 0 V.  250 volt 0 - 60 Hz

Advantages
  • High attenuation level for lower frequencies
  • Suitable for use under extreme conditions (military applications
  • Wear-resistant
  • Corrosion resistant

Applications
  • Shielded rooms
  • Shielded chambers
  • Anechoic chambers
  • Military applications

Shielding performance

8050 series - 8050-2-16 VS 8051-2-16

8050 VS 8051 - Power line filters for shielded cabinet

Please note: These values are measured under laboratory conditions. Results may vary in other situations; please read our Guarantee

Dimensional drawing
Power line filter diagram 8050

Diagram 1

Power line filter diagram 8050

Diagram 2

Happy to help
Allowed maximum size is 20 MiB. You can upload multiple files