Medium performance power line filter

Technology

  • Self-healing plastic film non inductive capacitor
  • Tinned metal case
  • Feed through mounting
  • Flame retardant V0
Medium performance power line filter

Mounting

These filters are designed to be mounted in directly on the entry panel of a Faraday cage or in a shielded filter housing.
Please contact us for options.

Torgue value max
Ø M 27 : 40 Nm
@ M 32 : 40 Nm

Connection

Treaded terminals with nut
Ø M 4 : 1.2 Nm
Ø M 6 : 2.45 Nm
Ø M 8 : 10 Nm
Ø M 10 : 15 Nm
Ø M 12 : 20 Nm

Models and ordering data

ReferenceCurrent
max.
LinesRated voltage UROperating
temperature
Test
voltage
Leakage current
@250V/50Hz
Curve
(A) AmountVDCVAC
50-60 Hz
VAC
400 Hz
ºCVDC(mA)Structure
MP - 2050 50 2 1000 250 - -40 +85 2121 86.4 1
MP - 2075 75 2 440 250 - -40 +85 800 812 2
MP - 2100 100 2 1000 250 125 -40 +85 2121 173 2
MP - 2100
type2
100 2 1000 250 - -40 +65 2121 86.4 1
MP - 2200 200 2 440 250 - -40 +85 800 812 2
MP - 2200
type2
200 2 1000 250 - -40 +65 2121 86.4 1
MP - 2300 300 2 440 250 - -40 +85 800 812 2
MP - 3050 50 3 1000 250 - -40 +85 2121 86.4 1
MP - 3075 75 3 440 250 - -40 +85  800 812 2
MP - 3100 100 3 1000 250 125 -40 +85  2121 173 2
MP - 3100
type2
100 3 1000 250 - -40 +65  2121 86.4 1
MP - 3200 200 3 440 250 - -40 +85  800 812 2
MP - 3200
type2
200 3 1000 250 - -40 +65 2121  86.4 1
MP - 3300 300 3 440 250 - -40 +85 800  812 2
MP - 4050 50 4 1000 250 - -40 +85 2121 86.4 1
MP - 4075 75 4  440 250 - -40 +85 800  812 2
MP - 4100 100 4 1000 250 125 -40 +85 2121 173 2
MP - 4100
type2
100 4 1000 250 - -40 +65 2121 86.4 1
MP - 4200 200 4 440 250 - -40 +85 800 812 2
MP - 4200
type2
200 4 1000 250 - -40 +65 2121 86.4 1
MP - 4300 300 4 440 250 - -40 +85 800 812 2
These values are measured under laboratory conditions.
In your situation results may differ, please read our Guarantee.

For the explanation of the reference see chapter how to order below


Attenuation characteristics

Medium performance power line filter Structure 1
Structure 1
Attenuation on load (50 Ω) MIL STD 220 A or GAM T 21
Medium performance power line filter Structure 2
Structure 2
Attenuation on load(50 Ω) MIL STD 220 A or GAM T 21

These values are measured under laboratory conditions.
In your situation results may differ, please read our Guarantee.


Dimensions in mm per filter

CurrentABCØ FLWeight (Gr.)Structure
50 A - - 115 - 192 820 2
75 A 41 17 92 M6 166 670 1
100 A 48 24 92 M8 180 750 1
100 A
type 2
- - 122 - 199 850 2
200 A 49 25 92 M10 172 950 1
200 A
type 2
- - 140 - 217 940 2
300 A 59 35 92 M12 194  1050 1

Mechanical data

Medium performance power line filter Structure 1
Structure 1
Medium performance po<wer line filter Structure 2
Structure 2

How to order

The picture below explaines how to generate a Medium performance part number.

  • Serie (MP = Medium performance)
  • Amount of phases
  • Current (A)
  • Type (See table)
  • Amount of volts
How to order a Medium performace power line filter

 

Would you like to...